Horne Engineering Ltd
FAULT FINDING CHART
REFER TO
SYMPTOM
POSSIBLE CAUSE
ACTION
SECTION
Temperature setting too
high.
Re- adjust temperature setting
4
Temperature has been set
when hot water
temperature is too low
Mixed water
Inspect Check Valve at cold
temperature too
Hot water has migrated into
3.6.1 to 3.6.6
inlet . If the check valve leaks
high
cold water supply
replace the strainer body and
See Drg.6397
check valve subassembly
Thermostat Element has
failed this can be checked
Replace element (8)
6
by carrying out a hot or cold
water failure test.
Temperature Setting too
Re- adjust temperature setting
4
low
Hot water supply
Check hot water supply
3.2
temperature has fallen
system
Mixed water
Inspect Check Valve at hot
temperature too
Cold water has migrated
inlet . If the check valve leaks
3.6.1 to 3.6.6
low
into hot supply
See Drg 6397
replace the strainer body and
check valve subassembly.
Cold valve face requires
Remove valve Cover (5) and
6.4.7
cleaning
service valve face
Partly blocked strainers
Clean strainers
6.2
Check all valves are full open.
Unusually high pressure
Check Pressurisation unit.
Mixed water flow
drop in supply pipework
Check mains supply
rate too low.
Extra Demand added to
Check pipe sizing
system
Valve requires de-scaling
Slide-Valve (9) is seized
6.4.5
Mixed water temp
Remove HORNE 15 TMV
does not respond
from pipes and reverse
to adjusting screw
Hot and cold inlets reversed
connections. Connect inlet
with red dot to hot pipe
Valve requires De-Scaling
Slide-Valve (9) is seized
6.4.5
Mixed water temp
Thermostat element has
changes and is not
failed (This can be checked
steady
Replace elements (8)
6
by carrying out a hot or cold
water failure test)
Hot inlet is marked with Red
Water at outlet
Hot and cold inlets are
dot.
runs full hot or full
reversed
Cold inlet is marked with Blue
cold
dot.
Valve continues to
Cold valve face requires
Remove valve cover (5) and
pass cold water
6.4.7
when hot supply is
cleaning
service cold valve face
isolated
Valve continues to
Fouling at hot valve seat
Clean hot valve face
6.4.7
pass hot water
Slide-Valve seal is
Replace Slide -Valve Seal
6.3.4 & 6.3.5
when cold supply
damaged
(13)
is isolated
Element has failed
Replace Element (8)
6
Page 10
Issue 2 19/09/05