Horne Engineering Ltd
pass hot water
Slide-Valve seal is
Replace Slide-Valve Seal (4)
6.2.5 & 6.2.6
when cold supply
damaged
is isolated.
Replace Thermostat Element/
Element has failed
6.2
Slidevalve Assembly (5)
If water flowing is more
than 4°C above required
mixed water temperature
then valve may not have
Recommission the valve,
been commissioned with an
closely following the guidance
3
adequate hot water supply
in Section 3.
temperature.
NB If this is the case the
valve may not offer scald
protection
If water flowing is not more
than 4°C above required
mixed water temperature
Repeat test with hot water
then the boiler is not
heating the water supply
temperature at least 5°C above
sufficiently to cause thermal
required mixed water temp.
shut-off. (N.B. this is
possible with combi
boilers).
Issue 3 Dec 05
Page 10 of 10